A packaging PLC's baseline is cyclic controller traffic only. The visibility tool now also shows that PLC sending cleartext HTTP to a new host. Which issue is that?
Select an answer to reveal the explanation.
Short Explanation
Your baseline includes the cell’s cyclic traffic, not every kind of communication. Seeing the PLC open a cleartext web session to a new host is a protocol deviation worth investigating; leave the normal cyclic traffic alone and find out who taught the controller to browse.
Full Explanation
Protocol deviation means the controller is using a protocol or peer absent from its baseline. Cleartext HTTP from the packaging PLC to a new host is not cyclic I/O; it is the unexpected communication to investigate. The usual cyclic traffic is the process continuing, so removing it first could stop the line while leaving the new session unexamined. A nightly historian file copy does not fit the evidence: the observation identifies HTTP sourced by the PLC, not a historian transfer mislabeled as PLC traffic. A wireless survey measures radios; it does not rewrite cyclic I/O frames as cleartext web traffic. An approved outbound HTTP client or telemetry function may explain a request to a server, but an inbound diagnostic web page alone does not explain the PLC initiating an outbound session. Verify direction and authorization. As an exam caveat, a new protocol or peer is a deviation even if the traffic is cleartext HTTP and the cyclic traffic remains normal. For a practical check, record the destination and session, confirm they are absent from the baseline, and block the session at the cell edge until operations explains it.