Cisco Cyber Vision reports a new activity on a brewery fermenter PLC: an engineering station performed a program upload and took a copy of the controller logic. No change ticket exists. Which reading fits?
Select an answer to reveal the explanation.
Short Explanation
A program upload is someone photocopying the recipe out of the cabinet, not a glance at the temperature gauge. You are watching controller logic leave the fermenter PLC with no ticket on the board. A nightly archive or a valve cycle does not copy that program.
Full Explanation
Cisco Cyber Vision builds activities from industrial traffic it decodes, and a program upload is a transfer of controller logic rather than a poll of live tags. The engineering station copied the fermenter PLC program and no change ticket accounts for it, so the sound reading is that logic left the controller. A nightly historian archive is a file that system writes for process history. It is not a PLC program upload, and a decoder that identified the upload did not invent the event from a rollup. Cyclic exchange with a valve manifold moves ordinary process values. That pattern is not a full logic upload unless the activity really was a program transfer. GOOSE is Layer 2 multicast among substation protection devices. It does not refresh brewery controller logic and it does not explain this report. Exam caveat: a ticketed upload can be legitimate maintenance. The reading still starts from the action that occurred, and a missing ticket is what keeps the event open, not a reason to rename the activity. Operational check: compare the station, the PLC, and the upload time with the brewery change log before anyone closes the finding.