After a core-switch change at a water plant, a clarifier PLC and its HMI are up in VLAN 40 on access ports of two different switches, but they cannot communicate. The trunk between the switches does not list VLAN 40. Which fault explains the outage?
Select an answer to reveal the explanation.
Short Explanation
The two switches are buildings, and VLAN 40 is a hallway the skybridge refuses to carry. You can see both closets lit and still have no path between the clarifier PLC and its HMI. The trap is chasing a certificate or a voice setting while the trunk list simply leaves that VLAN out.
Full Explanation
Two access ports in VLAN 40 can both be up and still have no path between them when they sit on different switches. The trunk has to carry VLAN 40. If the allowed-VLAN list omits 40, frames for the clarifier PLC and the HMI are not forwarded across that link, which matches a trunk the stem says does not list VLAN 40. A certificate wait on an enterprise VLAN would mean the HMI had left VLAN 40. The stem says the HMI access port is up in VLAN 40, so the HMI has not moved and a certificate is not the break. Voice VLAN configuration does not err-disable a port merely because the data VLAN number is 40, and an err-disabled port would not be up. A data diode is a one-way device installed on a path by design. Nothing in the stem places a diode between these access ports, and the two hosts are separated by a trunk that is missing their VLAN. Exam caveat: the stem already states the omission. Do not replace that fact with a certificate story or a voice-VLAN story the report does not show. Operational check: show interfaces trunk on both ends should list VLAN 40 as allowed once the change is made, and the access ports should still be in VLAN 40 when the HMI and PLC ping.