An irrigation HMI can ping its PLC, and both ports are up in the correct VLAN. Modbus TCP to port 502 fails. The ACL on the path permits ICMP and denies TCP 502. Which fault explains it?
Select an answer to reveal the explanation.
Short Explanation
You can trust the ping as proof that basic reachability works, while the ACL is the barrier stopping Modbus TCP on port 502. Since both ports are in the correct VLAN, you should check the ACL rather than move the PLC to another VLAN.
Full Explanation
Ping succeeds, both ports are up, and both are in the correct VLAN, so basic reachability is working. The fault is the path ACL: it permits ICMP but denies TCP port 502, which Modbus TCP uses. That rule directly explains why ping works while the Modbus connection fails. A wrong-VLAN fault does not explain the selective block of Modbus when the ports are confirmed to be in the correct VLAN; VLAN placement does not selectively deny TCP 502. Name resolution is not needed when the HMI connects to the PLC by address, and ping to that address already succeeds. A duplex mismatch can cause errors or poor performance across a link, but it does not account for an ACL explicitly permitting ICMP and denying one TCP port. Exam caveat: after correcting the deny, limit the permit to the HMI’s address rather than allowing any source. Practical check: use show ip access-lists to confirm hits on the deny for the HMI, then verify that the corrected permit receives hits and a Modbus read from the HMI succeeds.