During a winter freeze, a main valve feeding the facility's automatic sprinkler system malfunctions and must be shut off for repairs that will keep the system out of service for more than 10 hours. Which life-safety measure must the administrator implement for the affected area until the system is restored?
Select an answer to reveal the explanation.
Short Explanation
When your sprinkler system is out of service, you need trained people actively watching the affected area until it is restored. A continuous fire watch with fire-department notification protects you better than locking exits or relying on reminder signs, and avoids an unnecessary full-building relocation.
Full Explanation
Under 42 CFR 483.90(a)(8), when the automatic sprinkler system is out of service for more than 10 hours, the facility must evacuate the affected portion or establish a fire watch until the system is restored. Because the outage here exceeds that threshold, a continuous fire watch with local fire-department notification is the appropriate compensatory measure for the affected area; dedicated staff can detect a fire early while repairs proceed. The CFR text does not itself require fire-department notification, but notifying the department alongside continuous rounds is the best listed response and aligns with Life Safety Code practice. Relocating all residents from the building to partner facilities is disproportionate: the rule permits a fire watch instead of evacuation, and a full-building transfer can create trauma and clinical risk. Locking exterior exit doors to prevent wandering would obstruct required egress, especially when suppression is impaired. Signs at nurses’ stations telling staff to unplug personal space heaters are passive reminders, not active monitoring of rooms, corridors, and utility areas. As an exam caveat, the rule allows evacuation of the affected portion as an alternative; it does not make a fire watch the only permissible measure. In practice, confirm that fire-watch staff have no competing duties and document their rounds until sprinkler service is restored.
Prefer to study offline? Printable PDF study book + test engine ($7.50, unofficial). These questions stay free here.