Logs on a Cisco IE switch show a long run of failed SSH logins from a single address against the VTY. Which control slows that guessing?
Select an answer to reveal the explanation.
Short Explanation
Someone is rattling the same lock. You configure login block-for so a burst of SSH failures quiets the VTY for a while. The trap is opening Telnet beside SSH and calling that a dilution strategy.
Full Explanation
IOS login block-for, with a threshold of attempts inside a window, temporarily blocks further login attempts after too many failures. That slows a guess against SSH without deleting the accounts operators still need. Adding Telnet gives the same guess a second door. Removing every local username can lock out the plant if no other authentication is working. Moving the management address onto the PLC VLAN hides nothing useful and mixes administration with control traffic. The caveat is that a lock must be long enough to matter and short enough that a fat-fingered engineer is not shut out of a real incident for the whole shift. The check is a controlled test: after the configured failures, a further attempt should be refused, and a valid login should work again when the quiet period ends. Put the before-and-after evidence in the work order, including the interface or account you changed, the time, and the person who approved it. On the next shift, confirm the original symptom is gone and that the change did not open a second path while closing the first. If the process is still inside a live batch, leave the controller running and finish only the part of this work that does not restart it. That sequence keeps a correct fix from turning into an unplanned outage.