A gas-processing site calls the compressor network air-gapped because it has no permanent wide-area circuit. Contractors still dock laptops inside the compressor panel. Which position is sound?
Select an answer to reveal the explanation.
Short Explanation
A fence with no road still fails when you carry a door in your pocket. Docking a laptop in the compressor panel ends the air gap the moment that laptop can touch a controller. The missing wide-area circuit is not a strategy.
Full Explanation
An air gap is a claim that nothing crosses into the control network. A contractor laptop docked in the compressor panel is a crossing. It can carry files, malware, or a programming session onto a controller even when the site has no permanent wide-area circuit. The sound position is that the laptop is a path that must be controlled, even without that circuit. Treating the missing circuit as sufficient ignores the path that is actually used. A laptop does not need an enterprise route to change logic on a controller it is plugged into. A locally connected standalone laptop does not necessarily create an external network bridge. Verify its interfaces, approved files, and programming access. Putting compressor-curve confidentiality above keeping the unit online reverses the usual OT order. Confidentiality of operating data matters, and it does not define whether the network is isolated. Flattening the cell onto the enterprise LAN would add a permanent path and make the isolation claim worse, not repair the laptop problem. Operational check: list every port where a laptop can dock, confirm each visit has a ticket, and stop describing the compressor network as air-gapped on the architecture drawing.