A well-field crew says the pump PLCs are protected by an air gap because no permanent cable reaches the office, yet engineers carry a laptop between email and the PLC cabinet every week. Which statement fits?
Select an answer to reveal the explanation.
Short Explanation
An air gap is a moat, and a laptop in the truck is a drawbridge the moat did not approve. You cannot call the well field isolated while that laptop reads mail in the morning and programs pumps after lunch. The trap is trusting a missing permanent cable more than the way the crew actually works.
Full Explanation
An air gap means there is no path for data or malware between the controllers and other networks. A laptop that reads email and then programs pump PLCs is that path, carried by hand. Air-gapped networks can still face carried-media and laptop threats. Record physical network isolation separately from the risks of approved transfers. The missing permanent cable does not preserve the gap while this weekly practice continues, so the crew cannot treat the air gap as the security strategy. Antivirus on the laptop is a control on one computer. It does not recreate physical isolation for every pump, and a missed detection still rides into the cabinet. A diagram from last year records what someone drew. It does not override a laptop that moves between mail and the PLC this week. The strategy has to match the way engineers actually work, not the picture that omitted them. Calling the field isolated while the same laptop holds both mailbox data and the programming software is how an air-gap claim quietly expires. Exam caveat: a controller that truly has no walk-up programming path is a different situation from this well field. This stem's fact is the laptop, and that fact retires the claim. Operational check: write down the laptop's two uses in the same week, and stop marking the pump network as air-gapped on the current diagram while that practice remains.