In the Purdue model, where does a power-plant cooling-tower temperature probe belong if it only measures the process and runs no control logic?
Select an answer to reveal the explanation.
Short Explanation
That probe is a thermometer on the tower, not a brain that opens a valve. You place it at Level 0 with the process it measures. The trap is promoting the probe because its number also appears on a screen.
Full Explanation
Purdue Level 0 is the physical process: the water, the tower, and the sensors and actuators that touch it. A temperature probe that only measures and contains no control logic belongs there, even when a cable carries the reading to a controller. Level 1 is basic control, where a PLC or similar device decides and acts. The probe is an input to that controller, not the controller. Showing the same temperature on an operator graphic does not move the probe to Level 2. Level 2 is the supervisory layer, the HMI and the local operator view, and a value on a screen is a display of a Level 0 measurement. An enterprise energy dashboard is Level 4 business reporting. Copying a number onto that dashboard does not make the field device an enterprise system. Exam caveat: a transmitter with a small processor is still a process instrument when its job is to measure. The presence of electronics does not promote it into the PLC layer. Operational check: on the architecture drawing, the probe should sit with the cooling-tower instrumentation, and the PLC that commands fans or valves should sit at Level 1 above it.