A painting crew stages three 5-gallon cans of flammable lacquer thinner inside a commercial renovation wing for active spray-booth prep, and the nearest fire extinguisher is a 2A unit 90 feet away by the stairwell. What does OSHA 29 CFR 1926.150 require here?
Select an answer to reveal the explanation.
Short Explanation
You have 15 gallons of flammable lacquer thinner, so the specific Class B protection and shorter travel-distance rule apply. Keep a 10B-rated extinguisher within 50 feet of the liquid area; the 2A unit by the stairwell is not suitable protection for a solvent fire.
Full Explanation
Under OSHA 29 CFR 1926.150, when more than 5 gallons of flammable or combustible liquid are being used on a jobsite, a fire extinguisher rated at least 10B must be provided within 50 feet. Because you have 15 gallons of flammable lacquer thinner staged for active spray-booth preparation, both the Class B rating and the shorter travel distance apply. Moving the 2A extinguisher to 75 feet away does not meet the requirement: a 2A rating is for ordinary combustibles, not flammable liquids, and 75 feet exceeds the 50-foot limit. A pressurized water hose is not a substitute for the required extinguisher; water can spread burning solvent and increase the danger. Keeping the 2A unit 90 feet away because the work is temporary and ventilated also fails: neither condition removes the requirement triggered by using more than 5 gallons. Exam caveat: place the extinguisher unobstructed along the travel path, where a fire is unlikely to block access. Practical check: during daily walks, measure the actual walking distance from the liquid staging point to the nearest extinguisher rated at least 10B.
Prefer to study offline? Printable PDF study book + test engine ($7.50, unofficial). These questions stay free here.