A paint-blending shop installs a new listed flammable liquid storage cabinet inside its production bay to hold 1-gallon and 5-gallon metal cans of acetone and toluene, both Category 2 flammable liquids. Under OSHA 29 CFR 1910.106(d)(3), what storage rule applies to this cabinet?
Select an answer to reveal the explanation.
Short Explanation
A flammable storage cabinet buys your crew evacuation time during a fire, not unlimited storage space. The trap is treating a rated cabinet like an open warehouse shelf instead of capping Category 1 through 3 liquids at 60 gallons.
Full Explanation
Under OSHA 29 CFR 1910.106, you must limit Category 1 through 3 flammable liquids to 60 gallons per cabinet, while up to 120 gallons is permitted only for higher-flash-point Category 4 flammable liquids. Capping total volume keeps the thermal load within the cabinet's fire-resistance rating so internal containers do not rupture early during a fire. Choosing to store up to 240 gallons of Category 2 solvents inside a single metal cabinet quadruples the OSHA maximum per cabinet and creates an excessive fire hazard. Choosing to remove cabinet door latches so operators can access cans without delay defeats the three-point lock, with 18-gauge double walls, a 1.5-inch air space, a sill raised at least 2 inches, and the label "Flammable - Keep Fire Away" required to keep flames and radiant heat out. Choosing to co-locate nitric acid carboys inside the same flammable storage cabinet mixes strong oxidizing acids with organic solvents, risking violent reaction if a container leaks. Operationally, post a clear maximum-gallonage placard on the cabinet door and audit container volumes during monthly safety walk-throughs.
Prefer to study offline? Printable PDF study book + test engine ($7.50, unofficial). These questions stay free here.