During fueling of a barge-loading crane at a riverfront terminal, a hydraulic hose bursts and spills diesel fuel onto the dock, creating a visible sheen on the adjacent navigable river. Under Clean Water Act oil discharge rules in 40 CFR Part 110, what reporting action is required?
Select an answer to reveal the explanation.
Short Explanation
When oil hits navigable water, the federal threshold is not a specific gallon count—if you can see a sheen, the clock is already ticking. You must call the National Response Center immediately. The classic trap is waiting for a higher volume threshold or a routine monthly report.
Full Explanation
Under the Clean Water Act oil discharge regulations at 40 CFR Part 110, a harmful quantity of oil includes any discharge that causes a film or sheen upon or discoloration of the surface of navigable waters, requiring the person in charge to Immediately notify the National Response Center of any discharge causing a visible sheen. Wait until the monthly Discharge Monitoring Report is submitted to the state agency fails because routine NPDES wastewater reporting does not satisfy the immediate federal notification mandate for an accidental oil spill to surface water. Notify the National Response Center only if the spilled oil volume exceeds a thousand gallons fails because the sheen rule under 40 CFR 110.3 triggers immediate reporting regardless of how small the spilled volume is, whereas 1,000 gallons relates to separate SPCC spill-history thresholds. Submit an annual Tier II inventory update instead of making an immediate phone report fails because EPCRA Tier II reports track chemical storage inventories annually rather than emergency releases to waterways. As a regulatory caveat, state and local agencies often require parallel notifications under state spill rules. As an operational check, post the National Response Center toll-free number at dockside transfer stations and log the exact call time and report number.
Prefer to study offline? Printable PDF study book + test engine ($7.50, unofficial). These questions stay free here.