A cannery's controllers speak a cleartext plant protocol on an isolated VLAN, and no agent can be installed on them. Which control can see command writes on that VLAN?
Select an answer to reveal the explanation.
Short Explanation
The note you need is passed hand to hand in the plant, not through the front mailbox. You inspect the writes with a protocol-aware firewall on that VLAN. A web-proxy decryption, an agent the hardware cannot run, or an office mail gateway is on the wrong path.
Full Explanation
The writes are visible only on the VLAN that carries them, and they are already unencrypted, so a decryption proxy has nothing to terminate. Controllers of this kind cannot run an endpoint agent, so the host is not a place to look. A firewall on that VLAN, able to parse the plant protocol, is the control that sits on the flow, and mail inspection does not receive a copy of the command writes. A protocol-aware firewall on the plant VLAN that inspects writes between the controllers is the design that meets this requirement. TLS decryption on a web proxy the controllers do not use for this protocol is the wrong fit because the plant protocol is already cleartext and does not traverse the web proxy that would decrypt it. An endpoint agent on plant-controller hardware that cannot run a user agent is the wrong fit because the controllers cannot run an agent, so there is no endpoint at which to inspect the write. A mail data-loss gateway that sits on the office mail path, not the plant VLAN is the wrong fit because office mail is a different path, and the command writes stay on the plant VLAN with the controllers. Exam caveat: Seeing the write is not the same as a safe allow list of function codes, so confirm the firewall policy matches the commands the process is supposed to send. Operational check: From a lab controller, send a test write across the plant VLAN and confirm the firewall log shows the command, while the mail gateway and the web proxy show no copy of it.