A hospital is constructing a new inpatient medical unit that will include two Airborne Infection Isolation Rooms (AIIRs) for patients with pulmonary tuberculosis. Under CDC and ASHRAE ventilation guidelines for new construction, what minimum air change rate is required for these rooms?
Select an answer to reveal the explanation.
Short Explanation
Airborne isolation relies on rapid air dilution as well as negative pressure to protect your staff and adjacent patients. The trap is applying the older existing-facility threshold of six air changes per hour to brand-new hospital construction.
Full Explanation
Under CDC environmental infection control guidelines and ASHRAE Standard 170, newly constructed or renovated Airborne Infection Isolation Rooms must provide At least 12 air changes per hour (ACH) along with negative pressure relative to adjacent corridors and direct exhaust to the outside. Higher air change rates rapidly dilute and remove infectious droplet nuclei such as Mycobacterium tuberculosis from room air. Providing At least 2 air changes per hour falls far short of isolation standards and represents typical minimum outdoor air rates rather than total isolation dilution capacity. Selecting At least 6 air changes per hour is a common misconception because CDC guidelines allow 6 ACH only as a legacy minimum for existing AIIRs built prior to modern standards, not for new construction. Requiring At least 20 total air changes per hour exceeds the AIIR requirement and confuses AIIR ventilation with operating room standards. Exhaust outdoors for new AIIR construction; HEPA-treated recirculation exceptions depend on the applicable standard and retrofit constraints and do not automatically apply to these new rooms. Supplemental in-room HEPA does not remove outdoor-air requirements. As an operational check, partner with facilities engineering during commissioning to verify 12 ACH, continuous negative pressure differential, and alarm calibration before accepting the rooms for patient occupancy.
Prefer to study offline? Printable PDF study book + test engine ($7.50, unofficial). These questions stay free here.